4AI, 5DI, 6RO (CH1 RS232/opt., CH2, CH3 optional)
This system is gradually substituted by more modern and enhanced system TECOMAT FOXTROT and we do not recommend to use it in the new projects. More information you can find in category dedicated to PLC Tecomat Foxtrot. Tecoreg of series TR300 is a controller designed for medium to larger applications on the field of heating control, air-conditioning, boiler rooms, interchange stations, etc. in which no control panel or space separation of the control panel are required. A great number of communication possibilities predetermines the application of the controller also in extensive applications in co-action with other Tecoreg and PLC Tecomat controllers. The controller is freely programmable and thus usable for both in series repeated applications and of special customer orders.
Versions Basic module Type | AI | AO | DI | RO | Order number |
---|
TR301 | 4 | 0 (8)* | 5 | 6 | TXN 092 51 |
---|
TR302 | 4 | 4 | 5 | 6 | TXN 092 51 |
---|
TR303 | 8 | 0 (8)* | 10 | 10 | TXN 092 51 |
---|
TR304 | 8 | 4 | 10 | 10 | TXN 092 51 |
---|
* optional piggyback
Expansion module Typ | AI | AO | DI | RO | Order number |
---|
TR321 | 4 | 0 | 5 | 6 | TXN 092 71 |
---|
TR322 | 8 | 0 | 10 | 10 | TXN 092 72 |
---|
Technical features - Compact controller designed to be mounted in switchgears on a bar
- 4 versions of basic module, 2 versions of expansion module
- up to 20/20 binary inputs/outputs
- up to 16/8 analog inputs/outputs
- standardly 2 serial communication channels + 1 optional serial channel
- 32 kB program memory + 32 kB memory for texts on the display
- data memory expandable by up to 512 kB (Databox)
- graphic development environment MERKUR or programming in the language of instructions in the MOSAIC development environment
- the user program can be backed-up at EEPROM (optional)
- RTC circuit and parameters are backed-up in case of power failure
- connection to detachable screw-type terminal blocks
- power supply 24 V AC/DC
- digital outputs realized by a relay 250 V / 1 A to contact
- direct connection of temperature sensors Ni1000, OV1000
- indication of I/O status through a LED
- internal diagnostics
|